Page 127 - Altronix Product Guide
P. 127

FIRE
         RACK NAC POWER EXTENDERS

        R1042ULADA
        • UL Listed in the U .S . for Fire, UL 864 9th edition .
        • 10 amp @ 24VDC .
        • Four (4) Class A or four (4) Class B outputs with built-in sync protocols .
        • Fits two (2) 12VDC/17AH batteries .
        Enclosure dimensions: 3 .375”H x 19”W x 24”D





         Features:
         •  Two (2) Class A or two (2) Class B FACP inputs .  RAL1042ULADA
         •  Two (2) NC dry contact trigger inputs .                                        127
         •  Two (2) Class B outputs may be paralleled for more power
           on an indicating circuit .
         •  One (1) aux . power output @ 1 amp supply current   •  Built-in Cooper®, Gentex®,
           (with battery back up) .                 Potter® and System Sensor® sync protocols .
         •  One (1) aux . power output @ 1 amp supply current   •  Temporal Code 3, Steady Mode, Input to Output Follower Mode
           (without battery back up) .              (maintains synchronization of notification appliance circuits) .
         •  Signal circuit trouble memory-facilitates quickly locating intermittent  •  Compatible with 12VDC or 24VDC fire panels .
           system trouble and eliminates costly and unnecessary service calls .  •  Ground fault detection .
           LEDs indicate a prior fault (short, open, ground) has occurred on  •  AC fail, low battery and battery presence supervision .
           one or more signaling circuit outputs .  •  115VAC 60Hz . input .
         •  2-wire horn/strobe sync mode allows audible notification appliances   •  Includes cam lock and battery leads .
           (horns) to be silenced while visual notification appliances (strobes)
           continue to operate .

        altronix.com                                                                   ®
   122   123   124   125   126   127   128   129   130   131   132