Page 127 - Altronix Product Guide
P. 127
FIRE
RACK NAC POWER EXTENDERS
R1042ULADA
• UL Listed in the U .S . for Fire, UL 864 9th edition .
• 10 amp @ 24VDC .
• Four (4) Class A or four (4) Class B outputs with built-in sync protocols .
• Fits two (2) 12VDC/17AH batteries .
Enclosure dimensions: 3 .375”H x 19”W x 24”D
Features:
• Two (2) Class A or two (2) Class B FACP inputs . RAL1042ULADA
• Two (2) NC dry contact trigger inputs . 127
• Two (2) Class B outputs may be paralleled for more power
on an indicating circuit .
• One (1) aux . power output @ 1 amp supply current • Built-in Cooper®, Gentex®,
(with battery back up) . Potter® and System Sensor® sync protocols .
• One (1) aux . power output @ 1 amp supply current • Temporal Code 3, Steady Mode, Input to Output Follower Mode
(without battery back up) . (maintains synchronization of notification appliance circuits) .
• Signal circuit trouble memory-facilitates quickly locating intermittent • Compatible with 12VDC or 24VDC fire panels .
system trouble and eliminates costly and unnecessary service calls . • Ground fault detection .
LEDs indicate a prior fault (short, open, ground) has occurred on • AC fail, low battery and battery presence supervision .
one or more signaling circuit outputs . • 115VAC 60Hz . input .
• 2-wire horn/strobe sync mode allows audible notification appliances • Includes cam lock and battery leads .
(horns) to be silenced while visual notification appliances (strobes)
continue to operate .
altronix.com ®