Page 126 - Altronix Product Guide
P. 126
FIRE
RACK NAC POWER EXTENDERS
R1002ULADA
• UL Listed in the U .S . for Fire, UL 864 9th edition .
• 10 amp @ 24VDC .
• Two (2) Class A or four (4) Class B outputs with
built-in sync protocols .
• Two (2) NC dry contact trigger inputs .
• Fits two (2) 12VDC/12AH batteries .
Enclosure dimensions: 3 .375”H x 19”W x 24”D
R1002ULADA
Features:
126 • Two (2) Class A or two (2) Class B FACP inputs .
• Two (2) NC dry contact trigger inputs .
• Two (2) Class B outputs may be paralleled for more • Built-in Cooper®, Gentex®, Potter® and System Sensor® sync protocols .
power on an indicating circuit . • Temporal Code 3, Steady Mode, Input to Output Follower Mode
• One (1) aux . power output @ 1 amp supply current (maintains synchronization of notification appliance circuits) .
(with battery back up) . • Compatible with 12VDC or 24VDC fire panels .
• Signal circuit trouble memory - facilitates quickly locating intermittent • Common trouble inputs and outputs .
system trouble and eliminates costly and unnecessary service calls . • Ground fault detection .
LEDs indicate a prior fault (short, open, ground) has occurred on • AC fail, low battery and battery presence supervision .
one or more signaling circuit outputs . • 115VAC 60Hz . input .
• 2-wire horn/strobe sync mode allows audible notification • Includes cam lock and battery leads .
appliances (horns) to be silenced while visual notification (Batteries optional - order separately)
appliances (strobes) continue to operate . RE2R - Red Rack Battery Enclosure
888.258.7669
®