FIRE
         NAC POWER EXTENDERS

        AL642ULADA                  AL842ULADA                    AL1042ULADA
        • UL Listed in the U .S . for Fire, UL 864  • UL Listed in the U .S . for Fire, UL 864  • UL Listed in the U .S . for Fire, UL 864
          9th edition, CSFM and FM Approved .    9th edition, CSFM and FM Approved .    9th edition, CSFM and FM Approved .
        • 6 .5 amp @ 24VDC .        • 8 amp @ 24VDC .           • 10 amp @ 24VDC .
        • Four (4) Class A or four (4) Class B     • Four (4) Class A or four (4) Class B     • Four (4) Class A or four (4) Class B
          outputs with built-in sync  protocols .    outputs with built-in sync protocols .    outputs with built-in sync protocols .
        • Fits two (2) 12VDC/17AH batteries .  • Fits two (2) 12VDC/17AH batteries .  • Fits two (2) 12VDC/17AH batteries .
        Enclosure dimensions:       Enclosure dimensions:       Enclosure dimensions:
        18”H x 14 .5”W x 4 .625”D   18”H x 14 .5”W x 4 .625”D   18”H x 14 .5”W x 4 .625”D

         Features:
         •  Two (2) Class A or two (2) Class B FACP inputs .  •  Temporal Code 3, Steady Mode, Input to Output Follower Mode
         •  Two (2) NC dry contact trigger inputs .    (maintains synchronization of notification appliance circuits) .
         •  Two (2) Class B outputs may be paralleled for more power       •  Compatible with 12VDC or 24VDC fire panels .     125
           on an indicating circuit .             •  Ground fault detection .
         •  One (1) aux . power output @ 1 amp supply current   •  AC fail, low battery and battery   AL842ULADA
           (with battery back up) .                 presence supervision .
         •  One (1) aux . power output @ 1 amp supply current   •  115VAC 60Hz . input .
           (without battery back up) .            •  Includes cam lock
         •  Signal circuit trouble memory-facilitates quickly locating intermittent    and battery leads .
           system trouble and eliminates costly and unnecessary service calls .
           LEDs indicate a prior fault (short, open, ground) has occurred on
           one or more signaling circuit outputs .
         •  2-wire horn/strobe sync mode allows audible notification appliances
           (horns) to be silenced while visual notification appliances (strobes)
           continue to operate .
         •  Built-in Cooper®, Gentex®, Potter® and System Sensor® sync protocols .
                                                                      (Batteries optional - order separately)
        altronix.com                                                                   ®