Page 100 - Altronix Product Guide
P. 100
ACCESS
®
PANIC DEVICE POWER CONTROLLERS
Power Controller for Motorized Locking Devices
StrikeIt4
• Two (2) 19 .8VDC-26 .4VDC rated individually controlled
lock outputs configurable for fail-secure or fail-safe electronic
locking hardware for applications with battery back-up .
• Two (2) Normally Open (N .O .) trigger inputs (Input 1 and Input 2) .
• FACP Normally Closed (N .C .) input .
Features:
100 • Designed to handle the high current surge panic hardware • Trouble relay output
locking device(s) demand . indicating low AC voltage
• Built-in charger for sealed lead acid or gel type batteries . trouble and battery trouble .
• Input 115VAC, 60Hz, 2 .5A or 230VAC, 50Hz, 1 .5A . • Built-in charger for sealed lead acid batteries .
• Two normally open ADA inputs for special mode of • Automatic switch over to stand-by battery when AC fails .
interfacing with automatic door operators . • LED indicators:
• One (1) 19 .8VDC-26 .4VDC @ 0 .8A rated filtered regulated - AC Power LED indicates AC presence .
auxiliary output for applications with battery back-up, - Trigger output LEDs indicate panic device status / opened
24VDC-26 .4VDC @ 0 .8A rated for applications in US not (activated, short circuit) .
requiring battery back-up . Not affected by FACP trigger . - Fire Alarm Interface (FAI) indicates FACP interface is activated .
• One (1) 12VDC filtered regulated auxiliary output rated 0 .5A . - Battery LED indicates low battery during AC failure and
Not affected by FACP trigger . battery test .
• Two (2) follower Normally Open relay outputs for - AC status LED indicates loss of AC power .
controlling ADA actuators/accessories rated 28VDC @ 0 .5A .
• Two momentary door operator activation relay outputs .
888.258.7669
®