Page 28 - New Products Brochure
P. 28
COMMUNICATIONS
Provide Remote Indications of BBU & BDAS Status.
ANC1BBU
Remote Annunciator for COMMBATT1
- Allows local and remote annunciation of various trouble conditions
of BDA (Bi-Directional Amplifier) and BBU (Battery Back-Up Unit).
- Reports conditions to the FACP through separate set of dry contacts,
with visual and audible indicators.
EMERGENCY
- Nine (9) 10K EOL supervised inputs to connect to power supply and
other equipment that require annunciation of trouble conditions.
- Ten (10) NC output contacts to connect to FACP with convenient
end of line resistor wiring terminals.
- Separate relay NC output for reporting common trouble to FACP.
- Two (2) spare outputs for additional equipment monitoring.
- 12-24VDC input.
- Bi-color visual indicators of trouble conditions:
- AC Fail, Low Battery, Charger Fail, Component Fail,
BDA Fail and Antenna Fail ANC1BBU
Agency Listings:
- UL2524: Standard for In-building 2-Way Emergency Radio
Communication Enhancement Systems (US & Canada)
28