Specifications
Input
- Nominal 220VAC (working range 198VAC - 256VAC), 50/60Hz, 1.5A.
- Input fuse rated @ 5A/250V.
Output
- 12VDC or 24VDC selectable output.
- 12VDC or 24VDC @ 2.5A supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when switched over to battery backup.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery supervision (form "C" contacts).
- Battery presence supervision (form "C" contacts).
Visual Indicators
- AC input, DC output and Battery LED indicators.
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 15 BTU/Hr.
- 24VDC: 31 BTU/Hr.
- System AC input VA requirement: 374VA.
Dimensions & Weight
Dimensions (approximate):
- 4.5"W x 7.1"L x 1.44"H (114 mm W x 180 mm L x 37 mm H).
Weights (approximate):
- Product Weigtht: 0.65 Lbs. (0.29 kg).
- Shipping Weigtht: 0.8 Lbs. (0.36 kg).