ACMS12CB

Dual Input Access Power Controller, 12 PTC Protected Outputs, Board

Altronix ACMS12CB is a sub-assembly module designed to be used in Altronix wall and rack mount enclosures. Dual input design allows power to be steered from two (2) independent low voltage 5 to 24 VDC power sources into twelve (12) independently controlled PTC protected outputs. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. ACMS12CB will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in Fail-Safe or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the twelve (12) outputs. The spade connectors allow you to daisy chain power to multiple ACMS12CB modules. This feature allows you to distribute the power over more outputs for larger systems.

  • Input
      • Two (2) independent low voltage inputs.
        • 1) Input: 12 or 24VDC Altronix Power supply.
        • 2) Input: 12 or 24 VDC Altronix power supply or either 5 or 12 VDC from VR6 Regulator.
      • Voltage Range
        • 16A total input.
        • Main PTC Rating 9A.
      • Current Consumption:
        • 0.6A @ 12V, 0.3A @ 24V with all relays energized.
  • Trigger Inputs
      • Twelve (12) individually controlled trigger inputs:
        • a) Normally open (NO) inputs.
        • b) Normally closed (NC) inputs.
        • c) Open collector sink inputs.
        • d) Wet Input (5VDC - 24VDC) with 10K resistor.
        • e) Any combination of the above.
  • Outputs
    • PTC protected outputs rated @ 2A per output, Class 2 power-limited. Total output 16A max.
    • Do not exceed the individual power supply ratings.
    • Twelve (12) selectable independently controlled outputs or twelve (12) indepently controlled Fail-Safe or Fail-Secure power outputs.
    • Any of the twelve (12) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
    • Individual outputs may be set to OFF position for servicing.
  • Output Ratings
    • PTC are rated 2A each.
    • Total output current is determined by the power supply(ies), not to exceed a maximum of 10A for each input.
  • Fire Alarm Disconnect
    • Supervised: Latching or non-latching, individually selectable for any or all of the twelve (12) outputs.
    • EOL: 10K Resistor.
  • LED Indicators
    • Blue LED indicates FACP disconnect is triggered.
      • Individual voltage LEDs
        • Green: 12VDC
        • Red: 24VDC.
  • Temperature
    • Operating: 0ºC to 49ºC (32ºF to 120ºF).
    • Storage: -20ºC to 70ºC (-4ºF to 158ºF).
    • Relative Humidity 93% +/-5%.
    • BTU/Hr. (approx.): 4 BTU/Hr.
Dimensions (approximate):
  • 4.1"W x 7.3"L x 1.25"H (104.1 mm W x 185.4 mm L x 31.8 mm H).
Weights (approximate):
  • Product Weight: 0.7 Lbs. (0.32 kg).
  • Shipping Weight: 0.95 Lbs. (0.43 kg).